Modbus is simple, ubiquitous and completely untyped: the device gives you 16-bit registers and it is your job to know what they mean. QUBIQ's Modbus support is about making that mapping explicit and repeatable.

Configuration​

FieldDescription
NameConnection identifier.
HostDevice IP or hostname.
Port502 for Modbus TCP; the gateway's port for RTU-over-TCP.
Framing modetcp (Modbus TCP), rtu (RTU framing over a serial gateway), ascii.
Unit IDThe slave/unit address. 1 unless the device or gateway says otherwise.
Byte orderHow multi-register values are assembled — see below.
Connect timeout (ms)How long to wait for the socket.
Request timeout (ms)How long to wait for a response before failing the read.
Probe address / quantityThe register the connection test reads to prove the link.

Byte and word order​

The single most common source of wrong Modbus values. A 32-bit float spans two registers, and vendors disagree on the order of both the words and the bytes within them.

OrderAlso calledRegisters for 1.0f (0x3F800000)
Big-endianABCD0x3F80, 0x0000
Little-endianDCBA0x0000, 0x803F
Big-endian byte swapBADC0x803F, 0x0000
Little-endian byte swapCDAB0x0000, 0x3F80

If a value reads as an absurd number (4.6e-41, 1.7e38), the order is wrong — not the address. Read a register whose value you know, and try orders until it matches.

Register addressing​

Modbus has four address spaces. Which one you are reading is part of the address.

SpaceFunction codeAccessTypical notation
Coils1 / 5 / 15read/write bit0xxxx
Discrete inputs2read bit1xxxx
Input registers4read 16-bit3xxxx
Holding registers3 / 6 / 16read/write 16-bit4xxxx
Off-by-one

Vendor documentation is inconsistent about whether addresses are 0-based (protocol) or 1-based (documentation). Holding register "40001" in a manual is protocol address 0. If everything is shifted by exactly one, this is why.

Binding tags​

FieldNotes
RegisterThe register space (HR, IR, Coil, DI), the number, and 1-based addressing (datasheet) if you are typing the number from a manual. They compose the address, e.g. HR:100.
Byte / Word OrderABCD (default), CDAB, BADC, DCBA — see byte and word order. The width comes from the tag's data type.
Poll Rate (ms)Poll period, 1000 by default.

Modbus is strictly request/response: every Modbus tag is polled. The deadband is the tag's own, on its History tab.

Poll rate and register grouping​

QUBIQ groups contiguous registers into single requests. Two consequences:

  • Contiguous addresses are much cheaper than scattered ones. If you can influence the device's register map, block related values together.
  • Do not poll faster than the device can answer. A small PLC serving a serial gateway may manage a few requests per second. Polling every 100 ms produces timeouts, not fresher data.

Start at 1000 ms and reduce only where a faster value demonstrably matters.

Verifying a register​

Use Read registers in the connection's editor (needs View connections). It performs a one-shot read of a register range, so you can confirm an address and byte order before building tags on it.

Scaling​

Devices frequently transmit scaled integers: temperature as tenths of a degree, pressure as hundredths of a bar. Do not scale in every widget — configure it once on the tag:

Raw low 0 Eng low 0.0
Raw high 10000 Eng high 100.0

Scaling is applied after the read and before history and alarms, so everything downstream sees engineering units. → Tag properties

Writing​

Writable tags issue function code 5/6/15/16 depending on the target space and width. A write is acknowledged by the device; a failure surfaces as a rejected write, not a silent no-op.

Gate device writes with a write-security level on the tag so only sufficiently privileged runtime operators can drive equipment. → LiveView authentication

Troubleshooting​

SymptomCheck
Connection test times outWrong port; some devices use RTU-over-TCP on a non-502 port. Check the unit ID too.
Illegal data addressThe register does not exist, or the off-by-one above, or the wrong address space.
Illegal functionThe device does not support that function code — often read-only registers being written.
Values are nonsense floatsByte/word order.
Values are exactly 10× or 100× offMissing scaling.
Intermittent timeoutsPolling faster than the device or serial gateway can serve. Slow down.
One tag Bad, the rest fineThat register is outside a valid block; the grouped read fails for it only.