Your First Real Project

The Quick Start proved the pipe works. This page is about the decisions that make the difference between a project you can hand over and one that has to be rebuilt.

Decide the namespace shape first​

The tag path is the most permanent thing you will create. Screens, alarms, history, scripts and exports all reference it, and renaming a folder late means touching all of them.

Model the plant, not the network:

✅ Site1/Line1/Filler/Motor1/Speed
❌ PLC_192_168_1_10/DB12/Word4

A path organised around physical or process structure survives a PLC replacement, an IP change and a protocol migration. A path organised around addressing does not.

A workable convention, roughly ISA-95:

<Site>/<Area>/<Line or Cell>/<Equipment>/<Signal>

Rules that pay off later:

  • Be consistent about case and separators. Pick PascalCase or snake_case and hold the line.
  • No units in names. Speed, not Speed_RPM — the unit is a tag property.
  • No source hints in names. Temperature, not OPC_Temperature.
  • Keep depth even. Sibling equipment should sit at the same level, so wildcards and UDTs work.

Use user-defined types from the start​

If you have twenty identical motors, do not build twenty motor folders. Define a UDT once — members, data types, units, scaling, alarm definitions, binding address templates — and stamp out instances with parameters.

UDT: Motor
Speed float RPM address: ns=2;s={Device}.Speed
Current float A address: ns=2;s={Device}.Current
Running bool address: ns=2;s={Device}.Run
Fault bool address: ns=2;s={Device}.Fault alarm: on_boolean = true, priority high

Instance: Line1/Filler/Motor1 {Device} = "M101"
Instance: Line1/Filler/Motor2 {Device} = "M102"

Change the definition later and QUBIQ reconciles every instance. Instances with local overrides are reported as such rather than being silently overwritten.

→ User-defined types

Set engineering properties once, on the tag​

Resist the temptation to scale, format and range-check in each widget. Put it on the tag:

PropertyWhy on the tag
UnitWidgets, trends and exports all label from it
Raw/Eng scalingApplied after the protocol read, before history — so history is in engineering units
DeadbandKeeps noise out of history and broker egress, once for every tag that uses it
Format stringConsistent display everywhere the tag appears

→ Tag properties

Separate design-time and runtime identity early​

Decide before you build screens:

  • Who logs into the Platform? Those are platform users with permissions.
  • Who logs into LiveView? Those are runtime users in a User Database, with runtime roles.

Retro-fitting operator authentication after screens exist means revisiting every action that writes a tag. Deciding the write-security levels up front does not.

→ LiveView authentication

Structure views around navigation, not around drawing​

A screen tree that mirrors the namespace is easy to navigate and easy to hand over:

Overview plant-wide KPIs and alarm summary
Line1/Overview line status
Line1/Filler equipment detail
Line1/Capper equipment detail
Diagnostics connection health, service status

Use embedded views and flex repeaters so equipment detail is authored once and parameterised, exactly as UDTs do for tags. Twenty near-identical screens is the visualization version of twenty hand-built motors.

→ Views and layout

Write history deliberately​

History is cheap to enable and expensive to store. For each tag ask:

  • Does anyone trend this, or is live value enough?
  • What deadband makes the trend honest without storing noise? (A 0.5–1% of span deadband typically removes 90%+ of the rows and changes no chart a human can read.)
  • Does it need a store interval so a frozen signal still proves it was alive?

→ Historian configuration

Alarm rationalisation beats alarm volume​

An operator who ignores the alarm banner has no alarm system. Before adding an alarm, answer:

  1. Is it actionable? If nobody does anything differently, it is an event, not an alarm.
  2. What priority? Reserve critical for safety and production-stopping conditions. If everything is critical, nothing is.
  3. What delay and deadband? Nearly every chattering alarm is a missing on-delay or deadband.
  4. What does the message tell the operator to do? Put the response in the message text.

→ Configuring alarms

Version and back up​

  • Take a configuration backup at each milestone, and always before an upgrade.
  • Backups can be passphrase-encrypted, which is the only form that carries connection secrets.
  • The audit journal records who changed what; turn it on before you have anyone else in the system, not after an incident.

A checklist before hand-over​

  • Namespace follows one documented convention, top to bottom
  • Repeated equipment is UDT instances, not copies
  • Every tag has a unit, a description and a sane data type
  • History is on where it is needed, with deadbands
  • Every alarm is actionable, prioritised and has an operator-facing message
  • Screens reuse embedded views instead of duplicating layout
  • Platform roles grant the minimum needed; nobody shares the super admin
  • LiveView requires a login, and writable tags have write-security levels
  • The audit journal points at an external database
  • A restorable backup exists, and .env is stored separately
  • Connection health and service status are visible on a diagnostics screen

Next​

→ Platform architecture — how the pieces you just used fit together.